【规格】 交流无间隙金属氧化物避雷器
【备注】 金属氧化物避雷器
【类别】 电压保护装置
金属氧化物避雷器
产品名称:金属氧化物避雷器
产品备注:金属氧化锌避雷器
产品类别:电压保护装置
避雷器使用场所 |
型号 |
系统标称电压有效值kV |
避雷器额定电压有效值kV |
避雷器持续运行电压有效值kV |
直流1mA参考电压 ≥kV |
标称放电电流5kA |
通流容量 | |||
陡坡冲击电流残压 峰值≤ kV |
雷电冲击电流残压 峰值≤kV |
操作冲击电流残压 峰值≤kV |
2ms方波 |
4/10us大电流冲击≥kA | ||||||
低压型 |
HY1.5W-0.28/1.3 |
0.22 |
0.28 |
0.24 |
0.60 |
- |
1.3 |
- |
50 |
10 |
HY1.5W-0.5/2.6 |
0.38 |
0.50 |
0.42 |
1.20 |
- |
2.6 |
- |
50 |
10 | |
HY1.5W-0.58/3.2 |
0.48 |
0.58 |
0.46 |
1.4 |
- |
3.2 |
- |
75 |
35 | |
HY1.5W-0.62/3.6 |
0.52 |
0.62 |
0.5 |
1.6 |
- |
3.6 |
- |
75 |
35 | |
HY1.5W-0.8/3.9 |
0.66 |
0.8 |
0.68 |
1.8 |
- |
3.9 |
- |
75 |
35 | |
HY1.5W-0.9/4.3 |
0.69 |
0.9 |
0.72 |
1.9 |
- |
4.3 |
- |
75 |
35 | |
配电型 |
HY5WS-5/15 |
3 |
5 |
4.0 |
8.0 |
19.6 |
15.0 |
14.5 |
100 |
65 |
HY5WS-10/30 |
6 |
10 |
8.0 |
15.0 |
34.5 |
30.0 |
25.5 |
100 |
65 | |
HY5WS-17/50 |
10 |
17 |
13.6 |
25.0 |
57.5 |
50.0 |
42.5 |
100 |
65 | |
线路型 |
HY5WX-5/15 |
3 |
5 |
4.0 |
8.0 |
19.6 |
15.0 |
14.5 |
100 |
65 |
HY5WX-10/30 |
6 |
10 |
8.0 |
15.0 |
34.5 |
30.0 |
25.5 |
100 |
65 | |
HY5WX-17/50 |
10 |
17 |
13.6 |
25.0 |
57.5 |
50.0 |
42.5 |
100 |
65 | |
HY5WX51/134 |
35 |
51 |
40.8 |
73.0 |
154.0 |
134.0 |
114.0 |
600/800 |
65 | |
电 |
HY5WZ-5/13.5 |
3 |
5 |
4.0 |
7.5 |
15.5 |
13.5 |
11.5 |
200 |
65 |
HY5WZ-10/27 |
6 |
10 |
8.0 |
14.4 |
31.0 |
27.0 |
23.0 |
200 |
65 | |
HY5WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
51.8 |
45.0 |
38.3 |
200 |
65 | |
HY5WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
154.0 |
134.0 |
114.0 |
600/800 |
65 | |
发 |
HY5WD-4/9.5 |
3.15* |
4 |
3.2 |
5.7 |
10.7 |
9.5 |
7.6 |
400 |
65 |
HY5WD-8/18.7 |
6.3* |
8 |
6.3 |
11.3 |
21.0 |
18.7 |
15.0 |
400 |
65 | |
HY5WD-13.5/31 |
10.5* |
13.5 |
10.5 |
18.6 |
34.7 |
31.0 |
25.0 |
400 |
65 | |
HY5WD-17.5/40 |
13.8* |
17.5 |
13.8 |
24.4 |
44.8 |
40.0 |
32.0 |
400 |
65 | |
电 |
HY2.5WD-4/9.5 |
3.15* |
4 |
3.2 |
5.7 |
10.7 |
9.5 |
7.6 |
200 |
65 |
HY2.5WD-8/18.7 |
6.3* |
8 |
6.3 |
11.3 |
21.0 |
18.7 |
15.0 |
200 |
65 | |
HY2.5WD-13.5/31 |
10.5* |
13.5 |
10.5 |
18.6 |
34.7 |
31.0 |
25.0 |
200 |
65 | |
电机中性点型 |
HY1.5W-2.4/6 |
3.15* |
2.4 |
1.9 |
3.4 |
- |
6.0 |
5.0 |
200 |
65 |
HY1.5W-4.8/12 |
6.3* |
4.8 |
3.8 |
6.8 |
- |
12.0 |
1.0 |
200 |
65 | |
HY1.5W-8/19 |
10.5* |
8 |
6.4 |
11.4 |
- |
19.0 |
15.9 |
200 |
65 | |
HY1.5W-10.5/23 |
13.8* |
10.5 |
8.4 |
14.9 |
- |
23.0 |
19.2 |
200 |
65 | |
HY1.5W-12/26 |
15.75* |
12 |
9.6 |
17.0 |
- |
26.0 |
21.6 |
200 |
65 | |
HY1.5W-13.7/29.2 |
18.0* |
13.7 |
11.0 |
19.5 |
- |
29.2 |
24.3 |
200 |
65 | |
HY1.5W-15.2/31.7 |
20.0* |
15.2 |
12.2 |
21.6 |
- |
31.7 |
26.4 |
200 |
65 | |
电容器型 |
HY5WR-10/27 |
6 |
10 |
8 |
14.4 |
- |
27.0 |
21.0 |
400 |
65 |
HY5WR-17/46 |
10 |
17 |
13.6 |
24.0 |
- |
46.0 |
35.0 |
400 |
65 | |
HY5WR-51/134 |
35 |
51 |
40.8 |
73.0 |
- |
134.0 |
105.0 |
600/800 |
65 | |
变压器中性点 |
HY1.5W-30/80 |
35 |
30 |
24 |
44.0 |
- |
80 |
76 |
600/800 |
65 |
HY1.5W-33/90 |
35 |
33 |
26.4 |
48.0 |
- |
90 |
86 |
600/800 |
65 | |
HY1.5W-42/102 |
35 |
42 |
33.6 |
60.0 |
- |
102 |
95 |
600/800 |
65 | |
电气化铁道型 |
HY10WT-42/120 |
27.5 |
42 |
34.0 |
66 |
138 |
120 |
98 |
600/800 |
100 |
注:“*”表示电机额定电压有效值。
型号说明
本品依据GB11032-2010《交流无间隙金属氧化物避雷器》,以HY5WS-17/50为例对其型号说明如下:
Y:金属氧化物避雷器;
H:复合外套,无H即为瓷套;
5:标称放电电流,因电压等级而异;
W:无间隙,C:串联间隙,B:并联间隙;
S:配电型,Z:电站型,D:电机型,R:电容型,T:铁道型:
17:避雷器额定电压(kV),即允许加在避雷器上的最大允许工频电压有效值,因型号和电压等级而异。
50:标称放电电流下最大残压峰值(kV),因型号和电压等级而异。
使用条件
1) 环境温度:-40℃~+60℃;
2) 海拔高度:小于2000m(高于2000 m请选用高原型产品);
3) 额定频率:48Hz~62Hz;
4)最大风速不得超过35m/s;
5)地震裂度7度及以下地区;
试验项目
1)直流1mA参考电压:在避雷器两端施加直流电压,待流过避雷器的电流稳定于1mA后,读出的电压数值,该值不得小于技术参数表中的规定值。
2)泄漏电流:在避雷器的两端施加0.75倍直流1mA参考电压,此时流过避雷器的泄漏电流不大于50微安;
3)不得对本产品进行工频放电电压试验。